PROPERTY OF SOLIDSTATE CONTROLS, INC. 7/1998
A single phase UPS with a 120 V output can supply only a 120 V load. However, a three phase
UPS with a 208Y/120 V output can supply either a 120 V single phase load, a 208 V two phase
load, a 208 three phase load, or a 208Y/120 V, three phase load.
In determining the size of a three phase UPS, single phases loads can be distributed between
each of the three phases. However, one large single phase load can be connected to only one
phase of a three phase UPS. This one load may well determine the size of the system, even
though the other loads may be very small.
75.0 amp 1.5 amp 12.0 amp
.5 amp 5.0 amp
3.5 amp 1.5 amp
7.0 amp
2.5 amp
5.0 amp
3.0 amp
75.0 5.0 2.5 1 phase loads
7.0 3.0 1 phase loads
3.5 1 phase loads
0.5 1 phase loads
1.5 1.5 2 phase loads
12.0 12.0 12.0 3 phase loads
1.5 1.5 1.5 3 phase loads
5.0 5.0 5.0 3 phase loads
93.5 32.5 29.5
The actual minimum kVA required is calculated by multiplying the highest phase current times the
line-to-neutral voltage, times three, divided by 1000.
kVA = Amps (highest) x Voltage (line-to-neutral) x 3
` 1000
kVA = 93.5 x 120 x 3 = 33.66 kVA
100